User Interface

CVA User Interface

Set-up and Configuration

All setup and configuration is performed non-intrusively using a Bluetooth® enabled PDA running the Rotork Enlight software, which is freely downloadable from the website www.rotork.com

Each actuator is uniquely displayed on the PDA. Once the appropriate actuator is selected the LED on the actuator will flash blue.

Quick Setup Wizard

End-of-travel limit setting can be carried out automatically using the PDA auto setup wizard. During the setup wizard process, the CVA runs to the valve limit until it meets resistance, then backs off slightly and eases into the seat where the limit is then set, this is then repeated for the opposite direction.

During the quick setup procedure you can select the load (thrust or torque) to be limited for the duration of the setup, after which this can be set to match the process or control valve requirements. During the setup the actual measure load will be displayed.

After auto calibration the valve travel is shown on the PDA display.